Low and high pressure for GE GTS refrigerator.

I have a GE e GTS refrigerator. Is not culling despite change gas plenty times and filter tqo times. Also changes for any case starter and thermic switch. Low pressure i set it to 4 psi or a little more to test. Equalized pressure is form 55 to 75 depending on charge but don't cool or not freeze. I installed now a new filter with check valve to check high pressure. I need to know high working pressure at 28 °C ambient temperature. To check the compressor. Thanks in advance.

Answer this question I have this problem too

Is this a good question?

Score 0
6 Comments

Hi @dariolobos

What is the model number of the refrigerator?

by

General electric GTS

by

@dariolobos

There must be a model number somewhere on the product label and not just the model type?

For example something like this - GTS17BBSARWW or GTS18GSNRSS etc

by

General electric GTS 18

by

I am at work and the don't have the tag to see it

by

Show 1 more comment

Add a comment

1 Answer

Most Helpful Answer

Hi @dariolobos

At the moment I could only find the mini manuals for the GTS18DPC____, the GTS18GTH____, and the GTS18FCS____ model ranges.

They have the information that you need if your model is one of the ones in the models ranges listed.

Was this answer helpful?

Score 1

3 Comments:

All these manuals I have them. It mentioned only equalized pressure and not working pressure high pressure circuit. Maybe this I formation is in inspection and replacement of motor.

by

I need to check if capillary is not stocked or have partial obstruction. For that I need pressure limits in high pressure circuit. In some links I found vary between 150 to 200 psi. Being 150 the most recommended value but I need another source to confirm this.

by

@dariolobos

Even this GTS TSG doesn't show the full sealed system specifications

Does the compressor compliance plate show the current ratings for the motor?

If you have a clamp Ammeter check what the compressor start and run currents are

by